A/D Conversion Value Storage During Offset/Gain Setting - Mitsubishi Q64AD-GH User Manual

Melsec-q series, programmable logic controller, channel isolated high resolution analog-digital converter module with signal conditioning function
Hide thumbs Also See for Q64AD-GH:
Table of Contents

Advertisement

4 SETUP AND PROCEDURES BEFORE OPERATION
*2
Switches to offset/gain setting mode
Switches to normal mode

4.6.3 A/D conversion value storage during offset/gain setting

4 - 17
(b) When switching the mode using the setting of the mode switching setting
(buffer memory addresses 158, 159: Un\G158, Un\G159) and operation
condition setting request (Y9)
Common program
POINT
When switching the mode using the setting of the mode switching setting and
operation condition setting request, change the initial setting program for the
program marked
2.
(c) When switching the mode by making intelligent function module switch setting
Only the common program is necessary.
If during the offset/gain setting, the A/D conversion values are stored into the buffer
memory addresses 11 to 14, 54 to 61 (Un\G11 to Un\G14, Un\G54 to Un\G61) as in
the normal mode.
(1) Q64AD-GH
The A/D conversion values of all channels are stored into the buffer memory.
(2) Q62AD-DGH
The A/D conversion values of the channels specified in the offset/gain setting
mode (buffer memory addresses 22, 23: Un\G22, Un\G23) are stored into the
buffer memory.
MELSEC-Q
A/D conversion enable/disable
setting
Turns ON operation condition
setting request (Y9).
Sets 4144
to buffer memory
H
address 158.
Sets 964
to buffer memory
H
address 159.
Turns ON operation condition
setting request (Y9).
Sets 964
to buffer memory
H
address 158.
Sets 4144
to buffer memory
H
address 159.
Turns ON operation condition
setting request (Y9).
1-second timer
Turns OFF operation condition
setting request (Y9).