3 SPECIFICATIONS

3.1.3 Accuracy

3 - 9
The reference accuracy is the accuracy at the ambient temperature for offset/gain
setting.
The temperature coefficient is the accuracy per temperature variation of 1°C.
The reference accuracy is the accuracy relative to the maximum value of the digital
output value.
If you change the offset/gain setting or input range to change the input characteristic,
the reference accuracy and temperature coefficient do not vary and kept within the
ranges given in the performance specifications.
Example) Accuracy when the temperature varies from 25°C to 30°C
0.05% (reference accuracy) + 0.00714%/°C (temperature coefficient)
(temperature variation difference) = 0.0857%
MELSEC-Q
5°C