7 ONLINE MODULE CHANGE
MELSEC-Q
7.3.6 When user range setting is used and initial setting was made with sequence program

(other system is unavailable)

(1) Conversion disable
(a)
Set the A/D conversion enable/disable setting (buffer memory address 0:
Un\G0) for all channel conversion disable and turn operating condition
setting request (Y9) from OFF to ON to stop conversion.
After confirming that conversion has stopped with the A/D conversion
completion flag (buffer memory address 10: Un\G10), turn off Operation
Condition Setting Request (Y9).
(The screen shows the setting example of the Q64AD-GH.)
7 - 30
7 - 30