Mitsubishi Q64AD-GH User Manual page 29

Melsec-q series, programmable logic controller, channel isolated high resolution analog-digital converter module with signal conditioning function
Hide thumbs Also See for Q64AD-GH:
Table of Contents

Advertisement

3 SPECIFICATIONS
3 - 6
POINT
(1) Set within the analog input range and digital output range for each input range.
If these ranges are exceeded, the maximum resolution and accuracy may not
fall within the performance specifications. (Avoid use in the dotted area of Fig.
3.1.)
(2) Do not input an analog input voltage of more than ± 15 V. The input elements
may be damaged.
(3) Set the offset/gain values for the user setting range
the following conditions are satisfied.
(a) Offset value, gain value setting range: -10V to 10V
(b) { (gain value) - (offset value) } > 3.030V
(4) When an analog value that exceeds the range for the digital output value
entered, the digital output value will be fixed at the maximum or minimum value.
Analog input
range setting
1 to 5V
0 to 5V
-10 to 10V
0 to 10V
User range setting
(Uni-polar)
User range setting
(Bi-polar)
Digital output value (32 bits)
Minimum
Maximum
-1536
-65536
65535
-1536
-65536
MELSEC-Q
1 within a range in which
Digital output value (16 bits)
Minimum
Maximum
-768
-32768
32767
-768
-32768
3 - 6
2 is

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Sw2d5c-qadu-eQ62ad-dghGx configurator-ad

Table of Contents