Mitsubishi Q64AD-GH User Manual page 45

Melsec-q series, programmable logic controller, channel isolated high resolution analog-digital converter module with signal conditioning function
Hide thumbs Also See for Q64AD-GH:
Table of Contents

Advertisement

3 SPECIFICATIONS
Device No.
Signal Name
Operating
X9
condition setting
completed flag
3 - 22
(1) This signal is used as an interlock condition to turn ON/OFF the Operating condition
setting request (Y9) when any of the following settings has been changed.
• A/D conversion enable/disable setting (buffer memory address 0: Un\G0)
• CH
Average time/Average number of times/Move average/Time constant settings
(buffer memory addresses 1 to 4: Un\G1 to Un\G4)
• CH
A/D conversion starting time setting (buffer memory addresses 5, 6: Un\G5,
Un\G6)
• Averaging process specification (buffer memory address 9: Un\G9)
• Input signal error detection/warning output settings (buffer memory address 47:
Un\G47)
• CH
process alarm upper/lower limit value (buffer memory addresses 86 to 117:
Un\G86 to Un\G117)
• CH
rate alarm warning detection period (buffer memory addresses 118 to 121:
Un\G118 to Un\G121)
• CH
rate alarm upper/lower limit value (buffer memory addresses 122 to 137:
Un\G122 to Un\G137)
• CH
input signal error detection setting value (buffer memory addresses 138 to 141:
Un\G138 to Un\G141)
(2) When the operating condition setting completed flag (X9) is OFF, A/D conversion
processing is not performed. Under the following conditions, the operating condition
setting completed flag (X9) turns OFF.
• When operating condition setting request (Y9) is ON
Module ready (X0)
Operating condition
setting completed flag (X9)
Operating condition
change request (Y9)
A/D conversion
completed flag (XE)
Description
Performed by the A/D converter module
Performed by the sequence program
MELSEC-Q
3 - 22