6. PROGRAMMING
FEATURES
Factory
settings
of the constants
are shown
as [-""]
in the tables.
• Constant Set-up and Initialization
[ Constant
selection/initialization
(nO1)
I
The following
table describes
the data which
can be set or read when nO1 is
set.
Constant
that
Constant
that
Setting
can be set
can be referred
0
n01
n01 to n69
Constant writedisable
I
nO1to n60
nO1to n69
2 to 7
Not used (disabled)
8
Initialize
9
Initialize
(3owire sequence)*
Constant
Initialization
* Refer to page 47.
O-
E¢'¢" ,,
on the LED display for one second and the set data returns Io its
appears
initial values in the following
cases :
(I) The set values of input terminal function selection 1,2 and 3 (nO6, n07 and nO8) are the
same.
(2) If the following conditions are not satisfied in the torque pattern_setting(V/f pattern setting) :
Max. output frequency
(n24) > Max. voltage output frequency (n26)
> Mid. output frequency (n27)
> Min. output frequency (n29)
For details, refer to "Adjusting torque according Io application" (V/f pattern setting) on page
51.
(3) If the following condilions
are not satisfied in the Jump frequency setting :
Jump frequency 3 (n58) < Jump frequency 2 (n57)
< Jump frequency I (n56)
(4) If Frequency reference lower limit'(n42) < Frequency reference upper limit (n41)
a
(5) If Electronic thermal reference current (n3 I) < 120_/o of inverter rated currenl
(6) If the following is set when reverse run prohibit is set (n05=l) :
Reverse run is set by function LED["_"] or by FWD/REV run selection (nO4).
29