4.208 Maximum forward shift of optimum start
control
• Limitation of optimum start control
The forward shift of optimum start control can be limited to a maximum.
Setting range
00:00...06:00
The adjusted value will automatically be displayed on this operating line.
00:00
Optimum start control is switched off.

00:10 - Maximum forward shift of optimum start control

06:00
Optimum start control acts with or without room sensor.
The maximum forward shift can be set with parameter "Maximum forward shift
with optimum start control" (range is 0...6 h). This parameter can also be used
to switch optimum start / stop control off (setting = 0).
During non-occupancy hours, the heating is maintained at the reduced level. Towards
the end of the setback period, optimization switches the control back to the nominal
temperature level.
Optimization calculates the changeover time such that, at the start of occupancy, the
room temperature will have reached the nominal setpoint.
The forward shift is made with energy occupancy period.
4.208.1

Without room temperature sensor

The composite outside temperature is used as the compensating variable. In the case
of floor heating systems, the maximum forward shift should be longer than with radiator
systems. Using parameter KON, the forward shift can be matched to the building dy-
namics.
t
[min] = (12°C - TAgem) * KON * 1/16 * 10 [min]
E
Forward shift tE in hours and minutes with optimum start control without room sensor:
TAgem
0
- 20
0
- 10
0
0
0
+ 10
0
TAgem
Composite outside temperature
tE
Forward shift
KON
Parameter for quick setback and optimum start control (KON)
without room sensor (operating line 702
Parameter KON:
KON = 0:
Small KON:
Large KON:
Basic Documentation RVP540 / RVP550
Description of the heating engineer settings
Unit
hh:mm
KON
4
8
1h20
2h40
0h50
1h50
0h30
1h00
0
0h10
tE
)
EXP
Function deactivated
Note: KON also acts on quick setback
For buildings that can be heated up quickly
For buildings that can be heated up slowly
Factory setting
00:00
12
16
4h00
5h20
2h40
3h40
1h30
2h00
0h10
0h20
CE1P2488en
18.10.2002
20
6h00
4h30
2h30
0h20