Automatic Summer / Winter Changeover; Central Standby Switch - Siemens SIGMAGYR RVP540 Basic Documentation

Heat energy manager
Hide thumbs Also See for SIGMAGYR RVP540:
Table of Contents

Advertisement

Benefit
Description
Setting
Effect
Benefit
Description
Setting
Effect
D.h.w.
Display
258/348
Siemens Building Technologies
HVAC Products

4.249 Automatic summer / winter changeover

• Makes possible a uniform changeover of all heating circuits in the selected range of
action
Definition of action of automatic summer / winter changeover.
Summer / winter changeover of the selected range of action takes place when the
changeover temperature set on operating line 29 is reached.
Setting range
0 / 1
The setting will change the effect of summer / winter changeover:
Entry:
0
Local effect
Automatic summer / winter changeover switches the local heating circuit on and
off.
1
Central effect
Either the heating circuits of the segment or those of the entire system are
switched on and off by automatic summer / winter changeover, depending on the
selection made on operating line "Range of action of central changeover" (oper-
ating line 855).

4.250 Central standby switch

• Central operation of the interconnected system
Centrally from the RVP540 / RVP550, the entire heating system can be switched to
standby.
Setting range
0 / 1
Entry:
0
Central standby switching is deactivated
1
Central standby switching is activated
Either the heating circuits of the segment or those of the entire system are
switched on and off by automatic summer / winter changeover, depending on the
setting made on operating line "Range of action of central changeover (operating
line 855).
The central standby circuit does not affect d.h.w. heating. This means that the d.h.w. is
heated according to the settings made.
If the function is activated from the controller, the operating mode buttons
fected controllers in the segment or system will flash.
Basic Documentation RVP540 / RVP550
Description of the heating engineer settings
Unit
Unit
Factory setting
0
Factory setting
0
of all af-