4.5
Wiring
This section explains the wiring.
Wiring procedure
1.
Select the connection method
Select the connection method suitable to the application. (Page 74 Selecting connection method)
2.
Make arrangements for wiring
Prepare cables required for wiring. (Page 75 Cable)
3.
Turn OFF the PLC power
Before wiring, make sure that the PLC power is OFF.
4.
Wire the communication equipment.
Connect the RS-485 communication equipment. (Page 77 Connection diagram)
Selecting connection method
When using MC protocol 3C/4C frame, connection can be achieved in accordance with RS-232C or RS-485 (RS-422)
communication.
In FX5, it is possible to use a serial port for up-to a maximum of 4 channels simultaneously by using MC protocol.
Depending on each serial port, the available communication and channel number are decided.
In case of RS-232C communication (1:1)
For communication in accordance with RS-232C, it is 1-to-1 connection. Make sure that the total extension distance is 15 m or
less.
Personal computer
In case of RS-485 (RS-422) communication (1:N)
For communication in accordance with RS-485 (RS-422), up to 16 PLC Slave Nodes can be connected.
Make sure that the total extension distance is 1200m or less. (When using built-in RS-485 port or FX5-485-BD, 50m or less)
Personal computer
RS-232C/RS-485
communication
converter
FX-485PC-IF
4 MC PROTOCOL
74
4.5 Wiring
FX5 PLC
RS-232C
communication
equipment
FX5 PLC
Station No.0
RS-485
communication
equipment
FX5 PLC
Station No.15
RS-485
communication
equipment