Inverter Parameter Block Write - Mitsubishi MELSEC iQ-F FX5 User Manual

Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Inverter parameter block write

This instruction writes parameters of an inverter at one time
For information concerning inverter communication instruction expressions and execution format, refer to MELSEC iQ-F
FX5 Programming Manual (Instructions, Standard Functions/Function Blocks).
IVBWR
Ladder
(s1)
Setting data
■Contents, range, data type
Operand
Description
(s1)
Inverter station number
(s2)
Number of parameters in an inverter to be written at one time
(s3)
Head device number of a parameter table to be written to an
inverter
*1
(n)
Used channel
*2
(d)
Head bit device number to which instruction execution status is
output
*1 Specify a channel No. for which communication setting is set for inverter communication.
*2 Make sure not to use devices being used in other control operations. (Page 121)
■Applicable devices
Operand
Bit
X, Y, M, L, SM,
F, B, SB, S
(s1)
(s2)
(s3)
(n)
(d)
*1 T,ST and C cannot be used
Ex.
Writing contents in case of (s2): K8, (s3): D200
(s3)
D200
(s3)+1
D201
(s3)+2
D202
(s3)+3
D203
(s3)+14
D214
(s3)+15
D215
5 INVERTER COMMUNICATION
134
5.8 Programming
(s2) (s3)
(n)
(d)
Word
T, ST, C, D, W,
SD, SW, R
*1
*1
*1
Parameter No. 1
Parameter 1 value
Parameter No. 2
Parameter 2 value
(s2)×2 = Number of occupied word devices
Parameter No. 8
Parameter 8 value
ST
ENO:=IVBWR (EN, s1, s2, s3, n, d);
Range
K0 to 31
K1 to 4
Double word Indirect
U\G
Z
LC
Data type
16-bit signed binary
16-bit signed binary
16-bit signed binary
16-bit unsigned binary
Bit
Constant
specification
LZ
K, H
FBD/LD
EN
ENO
s1
d
s2
s3
n
Data type (label)
ANY16
ANY16
ANY16
ANY16_U
ANYBIT_ARRAY
(Number of elements:3)
Others
E
$

Advertisement

Table of Contents
loading

Table of Contents