Terminator

Use this element when a code or character string indicating the end of the packet is included.
Window
Item
Description
Element Name
Set the name of the element.
Code Type
Select a data type of the setting value.
• ASCII String
• ASCII Control Code
• HEX
Setting Value
Set data within 1 to 50 bytes.
The setting ranges that can be set for each code type are as follows:
• ASCII String: 20H to 7EH
• ASCII Control Code: 00H to 1FH, and control code of 7FH
• HEX: hexadecimal data of 00H to FFH
Considerations for configuring packet element
• Only one terminator can be used in a packet.
• A terminator can be set only at the end of a packet. Check code and static data only can be placed after the terminator.
Header
Data area
7 PREDEFINED PROTOCOL SUPPORT FUNCTION
Remarks
Setting example
• ASCII String: 'ABC'
• ASCII Control Code: ETX
• HEX: FFFF
Terminator
Check code
Static data
7.7 Packet Setting