5.6

Inverter Communication Settings

Before connecting an inverter to a PLC, set parameters related to communication in the inverter parameter unit (PU) in
advance.
For details on each function, refer to the inverter manual for each respective series.
Model
Model
classification
F800 Series
Inverter built in
A800 Series
Inverter built in
F700PJ Series
Inverter built in
F700P Series
Inverter built in
A700 Series
Inverter built in
E700 Series
Inverter built in
Option
E700EX Series
Inverter built in
D700 Series
Inverter built in
V500 Series
Inverter built in
Option
If these parameters are overwritten by the PLC after the inverter is connected, communication will be
disabled.
If these parameters are changed by mistake, they should be set again.

FREQROL-F800/A800 series

Connection destination: Built-in RS-485 terminal
Contents of communication setting (essential items)
The table below shows parameters which should be set in all cases.
Pr.
Parameter
Parameter item
group
331
N030
RS-485 communication station
332
N031
RS-485 communication speed
333
RS-485 communication stop bit length/
data length
N032
RS-485 communication data length
N033
RS-485 communication stop bit length
334
N034
RS-485 communication parity check
selection
337
N037
RS-485 communication waiting time
setting
341
N038
RS-485 communication CR/LF
selection
549
N000
Protocol selection
79
D000
Operation mode selection
340
D001
Communication startup mode selection
Connection
Relevant parameters
destination
RS-485 terminal
Pr.79, Pr.331 to Pr.342, Pr.549
P.N000, P.N001, P.N030 to P.N038, P.D000, P.D001, P.D010, P.D011
RS-485 terminal
Pr.79, Pr.331 to Pr.342, Pr.549
P.N000, P.N001, P.N030 to P.N038, P.D000, P.D001, P.D010, P.D011
PU port
Pr.79, Pr.117 to Pr.124, Pr.340, Pr.549
RS-485 terminal
Pr.79, Pr.331 to Pr.342, Pr.549
RS-485 terminal
Pr.79, Pr.331 to Pr.342, Pr.549
PU port
Pr.79, Pr.117 to Pr.124, Pr.340, Pr.549
FR-E7TR
PU port
Pr.79, Pr.117 to Pr.124, Pr.340, Pr.549
PU port
Pr.79, Pr.117 to Pr.124, Pr.340, Pr.549
PU port
Pr.79, Pr.117 to Pr.124, Pr.342
FR-A5NR
Pr.79, Pr.331 to Pr.342
Setting
value
0 to 31
48
96
192
384
576
1152
10
1
0
2
9999
1
0
0
1
Set conditions
Up to 16 inverters can be connected.
4800 bps
9600 bps
19200 bps
38400 bps
57600 bps
115200 bps
Data length: 7 bits
Stop bit: 1 bit
Data length: 7 bits
Stop bit: 1 bit
Even
Set in communication data
CR: Provided, LF: Not provided
Mitsubishi inverter (computer link) protocol
External operation mode is selected when power is turned ON.
Network operation mode
5 INVERTER COMMUNICATION
5.6 Inverter Communication Settings
Reference
section
Page 113
Page 113
Page 116
Page 115
5
Page 116
Page 117