If in doubt at any stage during the installation of the FX-50DU-TK(S)-C always consult a professional electrical engineer who is qualified and trained to the local and national standards. If in doubt about the operation or use of the FX-50DU-TK(S)-C please consult the nearest Mitsubishi Electric distributor. •...
Page 3
All examples and diagrams shown in this manual are intended only as an aid to understanding the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the product based on these illustrative examples.
Page 4
Graphic FX-50DU-TK(S)-C Units GRAPHIC FX-50DU-TK(S)-C UNITS Hardware Manual Manual number: JY992D64301 Manual revision: Date: January 1997...
Page 5
Graphic FX-50DU-TK(S)-C Units Guidelines for the safety of the user and protection of the FX-50DU-TK(S)-C units This manual provides information for the installation and use of the FX-50DU-TK(S)-C units. The manual has been written to be used by trained and competent personnel. The definition of such a person or persons is as follows;...
Page 6
Graphic FX-50DU-TK(S)-C Units The following variations of the FX-50DU-TK(S)-C conform to the identified standards;...
Graphic FX-50DU-TK(S)-C Units Table of Contents 1. Introduction 1.1 The Complete Family Of Graphic Data Access Units ..1-2 1.2 Dimensions and Specifications ....1-3 1.2.1 FX-50DU-TK(S)-C Dimensions .
Graphic FX-50DU-TK(S)-C Units Introduction Introduction This manual covers the hardware specifications and installation instructions for the following graphic data access units: FX-50DU-TK-C (monochrome) FX-50DU-TKS-C (STN; 8 colors) The Complete Family Of Graphic Data Access Units FX-25DU-E FX-30DU-E FX-40DU-TK-E 1 – 2...
Graphic FX-50DU-TK(S)-C Units Introduction Unit Accessories Each of the Graphic Data Access Units comes with the following accessories. The battery F -40BL is inside the unit and can be replaced by following the instructions later in this manual (Page 5-4). Figure 1.1 -40BL Mounting brackets and screws (6 of each) are...
Graphic FX-50DU-TK(S)-C Units Introduction Configuration Product descriptions and connection details are below. Figure: 1.6 Schematic System 1.5.1 Product Description 1.5.2 Connection Details FX-50DU-TK(S)-C Graphic Display Unit FX-40DU-CAB FX, FX or A series to monitor FX-40DU-CAB + FX-20P-CADP , FX , FX series to monitor F2-232CAB or compatible RS232 cable Serial Printer to print data logging and...
Graphic FX-50DU-TK(S)-C Units Introduction Function List The following table shows the various modes and the functions they support. Please refer to the DU software manual for further details. USER SCREEN MODE Activate the user screens MONITOR MODE DEVICE MONITOR Display/set device values ACTIVE STATE MONITOR Monitor STL (States) activity PC DIAGNOSTICS...
Graphic FX-50DU-TK(S)-C Units Introduction Set-up Mode As well as the functions listed in section 1.6 the FX-50DU-TK(S)-C can also adjust the following settings direct from the unit. To reach the set-up menu power on the unit while pressing the top left corner of the screen. Used for DU menus and SYSTEM LANGUAGE ENGLISH, JAPANESE...
Page 15
Graphic FX-50DU-TK(S)-C Units Introduction MEMO 1 – 8...
Graphic FX-50DU-TK(S)-C Units Terminal Layouts Terminal Layouts Following are the power terminals and the communication connectors assignments. Power Terminals Figure: 2.1 FX-50DU-TK(S)-C power terminals The FX-50DU-TK(S)-C power terminal on the back of the unit should be connected to an external 24VDC 24v DC power supply.
Page 18
Graphic FX-50DU-TK(S)-C Units Installation Notes Introduction Terminal Layouts Installation Notes Wiring Diagnostics Index 3 – 1...
Installation All the graphic data access units are intended to be installed in a panel and connected to a Mitsubishi PLC mounted inside the panel. Product Outline The figures below show the front and rear views of the FX-50DU-TK(S)-C, indicating the hardware features of the unit.
Graphic FX-50DU-TK(S)-C Units Installation Notes FX-50DU-TK(S)-C Dimensions Dimensions: mm (inches) 66 (2.60) (0.22) (4.72) (5.12) 160 (6.30) about 110 170 (6.69) Environment Specification Table: 3.2 SPECIFICATION. 0 to 40 °C 32 to 104 °F Operating temperature -20 to 60 °C -4 to 140 °F Storage temperature Humidity: No condensation 35 to 85% R.H.
Graphic FX-50DU-TK(S)-C Units Installation Notes Data Access Unit Mounting Cut a hole in the panel (1) to the appropriate dimensions as shown below. If required fit the seal (2) before inserting the unit into the panel. Insert the unit (3) squarely into the panel.
Graphic FX-50DU-TK(S)-C Units Installation Notes Control Devices The FX-50DU-TK(S)-C uses 8 bit devices and 6 data registers to enable control with the monitored MPU. The meaning of these devices is explained in the following table. Table: 3.3 Control Device Names Bit Devices Description Direction...
Graphic FX-50DU-TK(S)-C Units Wiring General Wiring The wiring of the Data Access Units has been designed to be safe and secure by using terminals for the connection of the power supply and D-Shell connectors for all communication cabling. Wiring Cautions •...
Page 26
Graphic FX-50DU-TK(S)-C Units Wiring Figure: 4.2 Connection to FX Service Supply Figure: 4.3 Connection to Independent Source Table: 4.1 Feature Table Table: 4.2 Power Supply Specification Ref.No. Spec. 24V DC Programmable Controller (MPU) Power Supply Voltage (+10%, –15%) Comms Cable FX-40DU-CAB Power Supply Ripple 200 mV or less FX-50DU-TK(S)-C...
Graphic FX-50DU-TK(S)-C Units Wiring Communication Cables The Data Access Units are connected to the MPU using the FX-40DU-CAB RS422 cable and to computers and printers using the F -232CAB cable or equivalent. • If the FX-40DU-CAB cable is not connected then a “communication error” may occur. •...
Graphic FX-50DU-TK(S)-C Units Diagnostics Diagnostics This chapter is intended to aid a trained engineer in fault finding and trouble shooting. Error Messages Screen messages and there meanings (in alphabetical order). BAD OBJECT EXISTS - - - XXXXXXX An incorrectly defined object (of type XXXXXXX) has been found when viewing a screen using test mode.
Page 30
Graphic FX-50DU-TK(S)-C Units Diagnostics PLC PROGRAM IS DESTROYED The program in the MPU has become corrupted. • Re-load the program in to the MPU. SET DEVICE IS INCORRECT Device Number entry: An invalid device number has been specified. Example: A word device (D) instead of a bit device (X,Y,etc.).
Display and Back Light The LCD life is about 50,000 hours and the back light life is about 10,000 hours operation. • User replacement is not possible. Please refer to your nearest Mitsubishi service centre. • For this reason it is recommended that a back light saving technique is used to extend the operational life time of the back light.
Page 35
Graphic FX-50DU-TK(S)-C Units Index MEMO 6 – 4...
Page 36
HARDWARE MANUAL GRAPHIC FX-50DU-TK(S)-C UNITS MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE: MITSUBISHI DENKI BLDG MARUNOUCHI TOKYO 100 TELEX: J24532 CABLE TOKYO HIMEJI WORKS: 840, CHIYODA CHO, HIMEJI, JAPAN Effective JAN. 1997 Specifications are subject JY992D64301A to change without notice.