Interrupt Module; Installation And Wiring - Mitsubishi MELSEC-Q Series User Manual

Programmable controller
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

1
GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE OF I/O
MODULE

1.2.5 Interrupt module

1.2.6 Installation and wiring

1 - 13
(1) If setting the response time during the interrupt input operation of QI60 or QX40H,
QX70H, QX80H, and QX90H, use the module whose contents are shown below.
The response time cannot be set with other contents (fixed at 0.2ms.).
Product name
PLC CPU
GX Developer
For how to check product information of the CPU module, refer to QCPU User's
Manual (Hardware Design, Maintenance and Inspection).
(1) Insulation-sleeved-solderless terminals cannot be used with the terminal block.
It is recommended to cover the wire connections of the solderless terminals with
mark or insulation tubes.
(2) Use wires of 0.3 to 0.75mm
terminal block. When using a wire whose core is 0.75mm or more, it is preferable to
use the spring terminal block(Q6TE-18S).
(3) Tighten the module fixing and terminal block screws to the torques in the following
ranges.
Screw location
Module fixing screw (M3 12 screw)
I/O module terminal block screw (M3 screw)
I/O module terminal block mounting screw (M3 screw)
Contents
Product information "021120000000000-B" or later
SW6D5C-GPPW or later
2
core and 2.8mm (0.11in.) OD max. to connect to the
MELSEC-Q
Tightening torque range
36 to 48 N•cm
42 to 58 N•cm
66 to 89 N•cm
1 - 13