Procedure Before Operation; System Configuration - Mitsubishi MELSEC iQ-F FX5 User Manual

Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

3.2

Procedure before Operation

The flow chart below shows the procedures from parallel link function setting to data link:
1.
Check communication specifications
For the communication specifications, link specifications, link time, link device numbers and number of link points, refer to
Page 52 Specifications.
2.
System configuration and selection
For the system configuration and selection of communication devices, refer to Page 51 System Configuration.
3.
Wiring
For the wiring with twisted pair cables and wiring examples, refer to Page 54 Wiring.
4.
*1
Communication setting
For the communication settings of communication devices, refer to Page 57 Communication Setting.
5.
Program creation
For the communication test program, master station program and slave station program, refer to Page 59 Programming.
*1 For details on operating procedures of GX Works3, refer to the manual below.
GX Works3 Operating Manual
3.3

System Configuration

This section outlines the system configuration required to use the parallel link function.
You can use the parallel link function in the CPU module using the built-in RS-485 port, communication board, and
communication adapter.
The serial port assignments are fixed to the following numbers, regardless of the system configuration.
■FX5U CPU module
CH4: Communication adapter-2
CH3: Communication adapter-1
CH1: Built-in RS-485 port
CH2: Communication board
Communication device
Built-in RS-485 port
Communication
FX5-485-BD
board
Communication
FX5-485ADP
adapter
*1 Assign CH3 and CH4 in the order from the adapter closest to CPU module.
In the parallel link, only one channel is available to use for one CPU module.
Serial port
Important points for selection
CH1
Since it is built-into the CPU module, there is no
need to add equipment.
CH2
Mounted on top of the CPU module, there is no
change in the installation space requirements.
*1
CH3, CH4
Mount the communication adapter to the left of the
CPU module.
■FX5UC CPU module
CH4: Communication adapter-2
CH3: Communication adapter-1
CH1: Built-in RS-485 port
3 PARALLEL LINK FUNCTION
3.2 Procedure before Operation
Overall distance
50 m or less
50 m or less
1200 m or less
3
51

Advertisement

Table of Contents
loading

Table of Contents