3.5
Wiring
This section explains about the wiring.
Wiring procedure
1.
Preparing for wiring
Prepare cables required for wiring. (Page 54 Cable)
2.
Turn OFF the PLC power
Before wiring, make sure that the PLC power is OFF.
3.
Wire the communication equipment
Connect the RS-485 communication equipment. (Page 56 Connection diagram)
Cable
Select cables using the procedure described below.
Twisted pair cable
Use shielded twisted pair cables for connecting RS-485 communication equipment.
The specifications of the cables used in wiring are shown.
■RS-485 cable specifications
Items
Cable type
Number of pairs
Conductor resistance (20)
Insulation resistance
Voltage resistance
Electrostatic capacitance (1 kHz)
Characteristic impedance (100 kHz)
■Cable structural drawing (reference)
Example of two-pair cable structural drawing
3 PARALLEL LINK FUNCTION
54
3.5 Wiring
Pair
Shield
Descriptions
Shielded cable
2p, 3p
88.0 Ω/km or less
10000 MΩ-km or more
500 V DC, 1 minute
60 nF/km or less as an average
110±10Ω
Example of three-pair cable structural drawing