2.5
Wiring
This section explains about the wiring.
For the wiring of FX3 PLC, refer to FX Series User's Manual - Data Communication Edition.
Wiring procedure
1.
Preparing for wiring
Prepare cables required for wiring. (Page 21 Cable)
2.
Turn OFF the PLC power
Before wiring, make sure that the PLC power is OFF.
3.
Wire the communication equipment.
Connect the RS-485 communication equipment. (Page 23 Connection diagram)
Cable
Select cables using the procedure described below.
Twisted pair cable
Use shielded twisted pair cables for connecting RS-485 communication equipment.
The specifications of the cables used in wiring are shown.
■RS-485 cable specifications
Items
Cable type
Number of pairs
Conductor resistance (20)
Insulation resistance
Voltage resistance
Electrostatic capacitance (1 kHz)
Characteristic impedance (100 kHz)
■Cable structural drawing (reference)
Example of two-pair cable structural drawing
Connecting cables
The table below shows applicable cables and tightening torques.
FX5U CPU module built-in RS-485 port
FX5UC CPU module built-in RS-485 port
FX5-485-BD
FX5-485ADP
Pair
Shield
Number of wires
connected per
terminal
One wire
Two wires
One wire
Two wires
Descriptions
Shielded cable
2p, 3p
88.0 Ω/km or less
10000 MΩ-km or more
500 V DC, 1 minute
60 nF/km or less by an average
110±10 Ω
Example of three-pair cable structural drawing
Wire size
Solid wire,
Wire ferrule with
Stranded wire
insulation sleeve
2
0.2 to 0.5 mm
0.2 to 0.5 mm
(AWG24 to 20)
(AWG24 to 20)
2
0.2 mm
(AWG24)
2
0.3 to 0.5 mm
0.3 to 0.5 mm
(AWG22 to 20)
(AWG22 to 20)
2
0.3 mm
(AWG22)
Tightening torque
2
0.22 to 0.25 N⋅m
2
2 N:N NETWORK
2.5 Wiring
2
21