Termination resistor setting
Set or connect termination resistor of the inverter farthest from the FX5 PLC.
For details on connection, refer to Page 107 Connection diagram.
At the FX5 PLC
The built-in RS-485 port, FX5-485-BD and FX5-485ADP have a built-in termination resistor.
Set the termination resistor selector switch to 110 Ω.
■FX5U CPU module built-in RS-485 port
■FX5-485-BD
At the Inverter
Communication may be affected by noise echo depending on the transmission speed and transmission distance. If
communication is hindered by noise echo, connect a termination resistor to the inverter.
■Built-in RS-485 terminal
A built-in termination resistor is provided. Connect a 100 Ω termination resistor to the inverter farthest from the PLC.
OPEN
Termination
resistor selector
switch
100
5 INVERTER COMMUNICATION
106
5.5 Wiring
Termination
resistor selector
switch
Termination
resistor
selector switch
■FX5UC CPU module built-in RS-485 port
■FX5-485ADP
Termination
resistor selector
switch
Termination
resistor selector
switch