Grounding
Grounding should be performed as stated below.
• Perform D class grounding. (grounding resistance: 100 Ω or less)
• Independent grounding should be performed for best results.
When the independent grounding cannot be performed, perform "shared grounding" as shown in the following figure.
For details, refer to the following.
MELSEC iQ-F FX5U User's Manual (Hardware)
MELSEC iQ-F FX5UC User's Manual (Hardware)
Other
PLC
equipment
Independent grounding
Shared grounding
(Best condition)
• The grounding wire size should be AWG 14 (2 mm
• Bring the grounding point close to the PLC as much as possible so that the ground cable can be shortened.
4.6
Communication Setting