Alarm, error and system messages
11.2 Error messages and error handling
No.
12
13
14
15
16
17
18
19
20
Error information FB1
See the section
11-8
Message
Description
Invalid
You have entered an illegal value in a
Netmask
subnet mask under Ports > Ethernet. The
value will not be used.
Must be a
The entered PROFINET station name
DNS-style
does not match the DNS convention.
Name
Hires not
You cannot operate a high-resolution
supported
sensor with this processing unit.
Hardware not
You cannot operate this firmware on your
supported
processing unit.
Loading
When starting processing or when a
model data.
model (set) is changed, the model data is
Please wait...
loaded and preprocessed. This can take
several seconds or even minutes
depending on the amount of data.
Model not
When working with an automation system,
trained
a model was selected that has not been
trained
Model set
When working with an automation system,
incomplete
a model set was selected that contains
untrained models
Different
When working with an automation system,
precisions
a model set was selected that contains
models with different precisions.
Model set too
When working with an automation system,
large
a model set was selected whose models
cannot all be loaded in memory at the
same time.
Control over an automation system (PLC, PC) / function block FB1
Remedies
The subnet mask must have the
form xxx.xxx.xxx.xxx with xxx =
0...255, and binary requires that
the left part be made up of ones
without a gap and the right part be
made up of zeros without a gap. In
addition, the 0.0.0.0 and
255.255.255.255 masks are not
allowed.
Use a low resolution sensor.
Use the system update to install
firmware that is valid for your
processing unit or use a
processing unit with a version that
supports this firmware version.
Check your model selection. If
necessary, retrain the model.
Remove the untrained model from
the model set or train the missing
model.
Based on Information -> Models,
check the precision of the models
in the set. If necessary, train
models
Remove the models from the
model set or reduce the number of
sub-ROIs in the individual models.
Check whether you could work with
lower precision.
Vision Sensor SIMATIC VS120
Operating Instructions, Edition 02/2006, A5E00757507-01