d3 Jump Frequencies

d3-01 Jump Frequency 1
d3-02 Jump Frequency 2
d3-03 Jump Frequency 3
Setting Range:
0.0 to 200.0 Hz
Factory Default: 0.0 Hz
d3-04 Jump Frequency Width
Setting Range:
0.0 to 20.0 Hz
Factory Default: 1.0 Hz
In order to avoid continuous operation at a speed that causes resonance in driven machinery, the Drive can be programmed with
jump frequencies that will not allow continued operation within specific frequency ranges. If a speed is commanded that falls
within a dead band, or Jump Frequency, the Drive will clamp the frequency reference just below the dead band and only
accept higher speed commands when the commanded speed rises above the upper end of the dead band, for increasing refer-
ences. Similarly, the Drive will clamp the frequency reference just above the dead band and only accept lower speed commands
when the command speed falls below the lower end of the dead band, for decreasing references.
d3-01
d3-04
d3-04
Setting the center point of the dead band with the d3-01 through d3-03 parameters and setting the width of the dead band with
parameter d3-04 determines the dead band characteristics. The programmer can set up to three Jump Frequencies. If multiple
Jump Frequencies are programmed the following rule applies:
d3-03
d3-02
d3-04
d3-04
Fig. 27 Jump Frequency Characteristics
d3-01 < = d3-02 < = d3-03
Programming 35
User Speed
Command Input
d3-03
d3-04