YASKAWA E7U Programming Manual page 67

Industrial hvac drive
Table of Contents

Advertisement

Option/Inv Function Input Status
To switch the command source between the serial communication port and the control circuit terminals be sure to program the
following parameters:
Set b1-01 (Frequency Reference Selection) to 1 (Terminals).
Set b1-02 (Run Command Selection) to 1 (Terminals).
Set H1-0x (Input Terminal Function Selection) to 6B or 6C.
The Com/Inv Sel 2 function will operate the same way except the logic is reversed. When a digital input is programmed for the
Com/Inv Selection function (H1-0x= 6C) that input will function as follows:
Option/Inv Function Input Status
IMPORTANT
Function: Auto Mode Sel
Setting: 6D
Function: Hand Mode Sel
Setting: 6E
The 6E setting for digital input defines the speed command (or setpoint) source as the keypad/operator for a closed contact and
allows b1-01 to determine the speed command source for an open contact.
Input Contact Status
This effects the speed command (reference) input only. The Auto Mode Selection (H1-0x=6D) and the Hand Mode Selection
(H1-0x-6E) allows use of a digital input to toggle between the Auto and Hand operational modes for speed control. The Auto
Mode Selection and Hand Mode Selection cannot both be programmed simultaneously. If both 6D and 6E are programmed
together, an OPE03 fault will occur.
OPEN
CLOSED
Table 16 6C, COM/INV SEL 2
OPEN
CLOSED
Switching the Reference and Run sources can only be done while the Drive is stopped.
OPEN
CLOSED
Table 15 6B, COM/INV SEL
Run and Speed Command Source
From the control circuit and analog input terminals (follows b1-01)
From Serial Comm port (R+,R-,S+, and S-) (embedded protocols)
Run and Speed Command Source
From Serial Comm port (R+, R-, S+, and S-) (embedded protocols)
From the control circuit and analog input terminals (follows b1-01)
Speed Command or PI Setpoint Source
Determined by b1-01
Keypad/operator (overide b1-01)
Programming 61