YASKAWA E7U Programming Manual page 151

Industrial hvac drive
Table of Contents

Advertisement

Parameter
Parameter Name
No.
Digital Operator Display
Motor Rated Current
E2-01
Motor Rated FLA
E2-03
No-Load Current
Motor Line-to-Line
E2-05
Resistance
Term Resistance
Operation Selection after
F6-01
Communication Error
Com Bus Flt Sel
Input Level of External Fault
from Communication Option
F6-02
Card
EF0 Detection
Stopping Method for
External Fault from
F6-03
Communication Option Card
EF0 Fault Action
Current Monitor Display Unit
F6-05
Selection
Current Unit Sel
Table A.1 Parameter List (Continued)
Description
Motor Setup
Set to the motor nameplate full load amps.
Sets the magnetizing current of the motor.
Phase to phase motor resistance, normally set by the autotuning
routine.
Com OPT Setup
Sets the stopping method for option PCB communications error
(BUS fault). Active only when a communications option PCB is
installed and when b1-01 or b1-02 = 3.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0: Always detected
1: Detected only during run
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0: A Display
1: 100%/8192 (Drive Rated Current)
Parameters A - 11
Setting
Factory
Menu
Range
Setting
Location
10% to
kVA
Quick Setting
200%
Dependent
kVA
kVA
Programming
Dependent
Dependent
0.000 to
9.842 Ω
Programming
65.000
0 to 3
1
Programming
0 or 1
0
Programming
0 to 3
1
Programming
0 or 1
0
Programming