H4 Analog Outputs

H4-01 Terminal FM Monitor Selection
Setting Range:
1 to 53
Factory Default: 2: Output Freq
The FM and AM analog output terminals can be programmed to output a 0-10 Vdc signal proportional to any one of functions
detailed in the table below.
Setting
1
2
3
6
7
8
15
16
18
* SFS is the internal soft starter signal. This signal is generated from the reference and often it passes through the accel/ decel functions.
When the H4-01 or H4-04 are configured the Drive will output 10Vdc to represent 100% of the function programmed into
them.
Function: Frequency Ref
Setting: 1
The analog output level will correspond to the chosen Speed Command input whether it is input via the digital operator, analog
input, or serial communication. 100% will be equivalent to the maximum output frequency of the Drive (E1-04).
Description
Frequency Ref
Output Freq
Output Current
Output Voltage
DC Bus Voltage
Output kWatts
Term A1 Level
Term A2 Level
Mot SEC Current
10 V
0
Fig. 59 Analog Output Signal Level as a Function of the Monitor Value
Programming 78
Table 19
Setting
20
24
31
36
37
38
51
52
53
100%
Monitor
Function Level
Description
SFS Output*
PI Feedback
Not Used
PI Input
PI Output
PI Setpoint
Auto Mode Fref
Hand Mode Fref
PI Feedback 2