H2 Digital Outputs - YASKAWA E7U Programming Manual

Industrial hvac drive
Table of Contents

Advertisement

H2 Digital Outputs

H2-01 Terminal M1-M2 Function Selection
H2-02 Terminal M3-M4 Function Selection
Setting Range:
0 to 3B
Factory Default: H2-01= "0: During Run 1"
H2-02= "A: Remote/Auto Oper"
The Drive has two multi-function outputs. By programming parameters H2-01 and H2-02, the user can assign specific
functions to each output. Below is a table with a complete list of all of the digital output functions. Following the table is a
more detailed description of each of the functions.
Parameter
setting
Function: During Run 1
Setting: 0
A "During Run 1"output will close whenever the Run command is provided and the Drive is outputting voltage.
This will include deceleration and DC Injection.
Function: Zero Speed
Setting: 1
The "Zero Speed" output will close whenever the output frequency falls below the Minimum Frequency (E1-09).
Function
0
During Run1
1
Zero Speed
2
F
/F
REF
OUT
3
F
/Set Agree 1
REF
4
Frequency Detect 1
5
Frequency Detect 2
6
Drive Ready
7
DC Bus Undervoltage
8
Baseblock 1
9
Option Reference
A
Remote Operation
B
Torque Detect 1 N.O.
C
Loss of Reference
Table 17 Digital Output Functions
Parameter
setting
Agree 1
10
11
12
17
1A
1E
1F
20
38
39
3A
3B
Programming 63
Function
E
Fault
F
Terminal Not Used
Minor Fault
Reset Cmd Active
Timer Output
Torque Detect 1 N.C.
Reverse Direction
Restart Enabled
Overload (OL1)
OH Pre-alarm
Drive Enable
Drive Waiting
Frequency Reduced, OH
Run from Serial Com