Parameter
Parameter Name
No.
Digital Operator Display
User Monitor Selection Mode
o1-06
Monitor Mode Sel
Second Line User Monitor
o1-07
Selection
2nd Monitor Sel
Third Line User Monitor
o1-08
Selection
3rd Monitor Sel
Frequency Reference Display
o1-09
Units
Frq Display Unit
Local/Remote Key Function
o2-01
Selection
Local/Remote Key
OFF Key Function During Auto
o2-02
Run
Oper OFF Key
User Parameter Default Value
o2-03
User Defaults
Drive/kVA Selection
o2-04
Inverter Model #
Frequency Reference Setting
o2-05
Method Selection
Operator M.O.P.
Operation Selection when Digital
o2-06
Operator is Disconnected
Oper Detection
Cumulative Operation Time
o2-07
Setting
Elapsed Time Set
Denotes that parameter can be changed when the drive is running.
** Factory settings change when b5-01=1 as follows: o1-06=1, o1-07=38, o1-08=24.
Table A.1
Parameter List (Continued
Description
Selects the "U1" monitors displayed on the 4th and 5th
lines of the digital operator display.
0: 3 Mon Sequential (Displays the next 2 sequential U1
monitors.)
1: 3 Mon Selectable (Displays U1 monitors set by o1-07
and o1-08.)
Sets the "U1" monitor always displayed on the 4th line
of the digital operator display. Effective only when o1-
06 = 1.
Sets the "U1" monitor always displayed on the 5th line
of the digital operator display. Effective only when
o1-06 = 1.
Sets unit display for the frequency reference parameters
and frequency related monitors when o1-03 ≥ 40.
0: WC:InchOfWater
1: PSI:lb/SqrInch
2: GPM:Gallons/Min
3: F:DegFahrenheit
4: CFM:Cubic ft/Min
5: CMH:Cubic M/Hr
6: LPH:Liters/Hr
7: LPS:Liters/Sec
8: Bar:Bar
9: Pa:Pascals
10: C:DegCelsius
11: Mtr:Meters
Key Selections
Has no function when HOA operator (Part# JVOP-162) is connected.
Determines if the off key on the digital operator will
stop the Drive when Drive is operating from external
terminals or serial communications.
0: Disabled
1: Enabled
Allows storing of current parameter values as a User
Initialization Selection at parameter A1-03.
0: No Change (No user parameter set active).
1: Set Defaults (Saves current parameter settings as user
initialization. A1-03 now allows selecting <1110> for
user initialization.
2: Clear All (Clears the currently saved user
initialization. A1-03 no longer allows selecting
<1110>.
Sets the kVA of the Drive. Enter the number based on
Drive Model #. Use the
CIMR-E7
Model Number.
Reference Appendix 2
Determines if the Data/Enter key must be used to input
a frequency reference from the digital operator.
0: Disabled - Data/Enter key must be pressed to enter a
frequency reference.
1: Enabled - Data/Enter key is not required. The
frequency reference is adjusted by the up and down
arrow keys on the digital operator without having to
press the data/enter key.
Determines if the Drive will stop when the digital
operator is removed.
0: Disabled - The Drive will not stop when the digital
operator is removed.
1: Enabled - The Drive will fault (OPR) and coast to
stop when the operator is removed.
Sets the initial value of the elapsed operation timer.
Parameters A - 24
)
Setting
Range
0 or 1
1 to 53
1 to 53
0 to 11
0 or 1
0 to 2
portion of the
0 to FF
0 or 1
0 or 1
0 to 65535
Factory
Menu
Setting
Location
0**
Programming
2**
Programming
3**
Programming
0
Programming
1
Programming
0
Programming
kVA
Programming
Dependent
1
Programming
1
Programming
0H
Programming