H1 Digital Inputs - YASKAWA E7U Programming Manual

Industrial hvac drive
Table of Contents

Advertisement

F6-03 Option PCB External Fault Stopping Method
Setting
0
Ramp to Stop
1
Coast to Stop (factory default)
2
Fast-Stop
3
Alarm Only
If an external fault is received from the L
determine the Drive operation in reaction to the fault signal. Parameter F6-02 will determine if the external fault is always
recognized (F6-02= "0: Always Detected") or only recognized when the Run command is active (F6-02= "1: Detected only
during operation").
Once the fault is recognized, parameter F6-03 will determine the operation of the Drive. If parameter F6-03 is set to anything
other then "3", the Drive will fault and a stopping sequence is begun. If F6-03= "3: Alarm Only", then the external fault is
treated like an alarm. Operation will continue and an EF0 fault will flash on the digital operator.
F6-05 Current Scaling via Communication Option PCB
Setting
0
A Display (factory default)
1
100%/8192 (Drive Rated Current)
A communication option card can read the Drive's DPRAM to access the current monitor. The format of the current reading
in the DPRAM will be determined by parameter F6-05.
F6-05= "0: A Display"
F6-05= "1: 100%/8192 (Drive Rated Current)"

H1 Digital Inputs

H1-01 Terminal S3 Function Selection
H1-02 Terminal S4 Function Selection
H1-03 Terminal S5 Function Selection
H1-04 Terminal S6 Function Selection
H1-05 Terminal S7 Function Selection
Setting Range:
0 to 6E
Factory Default: H1-01= "24: External Fault"
H1-02= "14: Fault Reset"
H1-03= "3: Multi-Step Ref 1" (2-Wire)
H1-04= "4: Multi-Step Ref 2" (2 Wire)
H1-05= "6: Jog Freq Ref " (2 Wire)
Description
ORKS ®
W
ON
Description
Current is a decimal number corresponding to actual Amperes
8192 = 100% of Drive rated output current
"0: 3-Wire Control" (3 Wire)
"3: Multi-Step Ref 1" (3 Wire)
"4: Multi-Step Ref 2" (3 Wire)
or other communication option card, the settings of F6-02 and F6-03 will
Current reading is a number where
Programming 45