Like the bias settings for the analog inputs (H3-03 and H3-11), the bias settings for the analog outputs determine the output
function level that will be equivalent to 0Vdc (or 4mA if the optional terminal board is used).
For example, if H4-03= -25%, then when the output function level is at 0% the FM analog output will output 2Vdc.
H4-04 Terminal AM Monitor Selection
Setting Range:
1 to 53
Factory Default: 8: Output kWatts
Refer to parameter H4-01 for description details.
H4-05 Terminal AM Gain Setting
Setting Range:
0.0 to 1000.0%
Factory Default: 50.0%
H4-06 Terminal AM Bias Setting
Setting Range:
-110.0% to +110.0%
Factory Default: 0.0%
Refer to parameters H4-02 & H4-03 for description details.
H4-07 Terminal FM Signal Level Selection
H4-08 Terminal AM Signal Level Selection
Setting
0
0 - 10 VDC (factory default)
1
4 - 20 mA
When the Drive is equipped with the optional, removable terminal board with 4-20mA outputs (p/n ETC618120), parameters
H4-07 and H4-08 determine whether analog outputs are configured as 0-10Vdc or 4-20mA. Refer to the documentation for
the optional terminal board as the proper jumper settings are required in addition to programming H4-07 and H4-08.
If the standard removable terminal board is being used, the settings of H4-07 and H4-08 have no effect.
100%
0
2V
-25%
Analog Output
Fig. 61
Description
Programming 82
10V