Monitor List - YASKAWA E7U Programming Manual

Industrial hvac drive
Table of Contents

Advertisement

Monitor List

Parameter
Parameter Name
No.
Digital Operator Display
Frequency Reference
U1-01
Frequency Ref
Output Frequency
U1-02
Output Freq
Output Current
U1-03
Output Current
Output Voltage
U1-06
Output Voltage
DC Bus Voltage
U1-07
DC Bus Voltage
Output Power
U1-08
Output kWatts
Input Terminal Status
U1-10
Input Term Sts
Output Terminal Status
U1-11
Output Term Sts
Drive Operation Status
U1-12
Int Ctl Sts 1
Table A.2 Monitor List
Description
Frequency reference (speed command) monitor when in auto
mode, frequency reference (speed command) setting location
when in hand mode. Units changeable via o1-03.
Output frequency (speed) monitor. Units changeable
via o1-03.
Output current monitor
Displays Drive output voltage
Displays DC Bus Voltage
Displays Drive output power
Displays Drive input terminal status
0
0 0 0 0 0 0 0
Output terminal ON/OFF Check
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
Parameters A - 26
Monitor
1: FWD. run
(Terminal S1) is ON.
1: REV. run
(Terminal S2) is ON.
1: Multi-function input 1
(Terminal S3) is ON.
1: Multi-function input 2
(Terminal S4) is ON.
1: Multi-function input 3
(Terminal S5) is ON.
1: Multi-function input 4
(Terminal S6) is ON.
1: Multi-function input 5
(Terminal S7) is ON.
1: Multi-function Contact 1
output 1 (Terminal M1-M2)
is ON.
1: Multi-function Contact 2
output 1 (Terminal M3-M4)
is ON.
Not used
Not used
1: Fault output
(Terminal MA/MB-MC) is
ON.
1: During running
1: During zero speed
1: During reverse
1: During reset signal input
1: During speed agree
1: Drive operation ready
1: During fault detection
(Minor fault)
1: During fault detection
(Major fault)