The Speed Search function can be turned on for all starts with parameter b3-01. If, however, it is beneficial to only use Speed
Search at certain starts, a digital input can be programmed to turn on Speed Search only when it is closed.
Speed Search 1 will start searching for the rotor speed from the maximum frequency (E1-04). Speed Search 2 will begin
searching for the rotor speed from the existing Speed Command. Speed Search 3 will cause the motor to baseblock when the
switch is open and then perform Speed Search when it closes.
In all cases the form of Speed Search, Speed Estimation or Current Detection, is determined by the setting of b3-01.
If b3-01= "0: SpdsrchF Disable", then the Speed Estimation form of Speed Search is used. If b3-01= "2: SpdsrchI Disable",
then the Current Detection form of Speed Search is used.
Function: Comm Test Mode
Setting: 67
The Drive has a built-in function for self-diagnosing the serial communications operation. The test involves wiring the send
and receive terminals of the RS-485/422 port together. The Drive transmits data and then confirms the communications are
received normally.
In order to perform the serial communications self-diagnosis, terminal S7 must be programmed as the Comm Test Mode
digital input (H1-05= "67: Com Test Mode") and then power removed from the Drive and the following steps performed:
1.Wire the S7 and SC terminals of the control circuit terminals together
2. Wire the R+ and S+ terminals of the RS-485/422 port together
3. Wire the R- and S- terminals of the RS-485/422 port together
4. Turn On the terminating resistance (Move Switch 1 of Dip Switch 1 to the ON position).
5. Turn on power to the Drive.
After step 5 above the Drive will either display "Pass" if everything is okay or a CE alarm will be displayed. If the CE alarm
occurs, the fault output contact will energize.
SC
S3
S1
S2
RP
R+
S1
O
1
1
F
F
2
Fig. 40 DIP Switch Setting for Terminating Resistor
Programming 59
S6
S4
S5
S7
R-
S+
S-
Terminating
resistance
DIP Switch S1 located on
removable terminal board.