YASKAWA E7U Programming Manual page 85

Industrial hvac drive
Table of Contents

Advertisement

Function: Output Freq
Setting: 2
The analog output level will correspond to the actual Speed being output by the Drive and will include the acceleration and
deceleration ramps. 100% will be equivalent to the maximum output frequency of the Drive (E1-04).
Function: Output Current
Setting: 3
The analog output level will correspond to the output current level of the Drive. 100% will be equivalent to the Drives rated
output current which is based on the kVA Rating of the Drive (o2-04).
Function: Output Voltage
Setting: 6
The analog output level will correspond to the output voltage level of the Drive. 100% will be equivalent to either 200Vac or
400Vac depending on the input voltage rating of the Drive.
Function: DC Bus Voltage
Setting: 7
The analog output level will correspond to the voltage level of the Drive's DC Bus. 100% will correspond to 400Vdc for the
240Vac input Drive and 800Vdc for the 480Vac input Drive.
Function: Output kWatts
Setting: 8
The analog output level will correspond to an internally calculated output power level based on the measured output current
and output voltage. 100% will correspond to the kilowatt rating of the Drive as determined by o2-04.
Function: Term A1 Level
Setting: 15
The analog output level will correspond to the analog input to the Drive's A1 terminal. 100% will be equivalent to 10Vdc.
Function: Term A2 Level
Setting: 16
The analog output level will correspond to the analog input to the Drive's A2 terminal. 100% will be equivalent to 10Vdc.
Function: Mot SEC Current
Setting: 18
The analog output level will correspond to the calculated secondary (torque producing) current. 100% will be equivalent to
motor's full load secondary current as calculated by:
2
Ι
I sec =
- I
Nameplate
no load
2
(E2-01)
=
- (E2-03)
Programming 79