YASKAWA E7U Programming Manual page 99

Industrial hvac drive
Table of Contents

Advertisement

Register No.
Sequence input status
002BH
Bits 7 to F
Drive status
002CH
Multi-function digital output status
002DH
Bits 3 to F
002EH - 0030H
Not used
0031H
Main circuit DC voltage
0032H - 0037H
Not used
0038H
PI feedback level (Input equivalent to 100%/Max. output frequency; 10/1%; without sign)
0039H
PI input level (±100%/±Max. output frequency; 10/1%; with sign)
003AH
PI output level (±100%/±Max. output frequency; 10/1%; with sign)
003BH
CPU software number
003CH
Flash software number
Communication error details
003DH
Bits 7 to F
003EH
KVA setting
003FH
Control method
Note: Communication error details are stored until an error reset is input (errors can be reset while the Drive is operating).
Table 24 Monitor Data
Bit 0
Input terminal S1
Bit 1
Input terminal S2
Bit 2
Multi-function digital input terminal S3
Bit 3
Multi-function digital input terminal S4
Bit 4
Multi-function digital input terminal S5
Bit 5
Multi-function digital input terminal S6
Bit 6
Multi-function digital input terminal S7
Not used
Bit 0
Operation
Bit 1
Zero speed
Bit 2
Frequency agree
Bit 3
Desired frequency agree
Bit 4
Frequency detection 1
Bit 5
Frequency detection 2
Bit 6
Drive startup completed
Bit 7
Low voltage detection
Bit 8
Baseblock
Bit 9
Frequency reference mode
Bit A
Run command mode
Bit B
Overtorque detection
Bit C
Frequency reference lost
Bit D
Retrying error
Bit E
Error (including Modbus communications time-out) 1:Error occurred
Bit F
Modbus communications time-out 1: Timed out
Bit 0
Multi-function digital output 1 (terminal M1-M2) 1: ON 0: OFF
Bit 1
Multi-function digital output 2 (terminal M3-M4): 1: ON 0: OFF
Bit 2
Not used
Not used
Bit 0
CRC error
Bit 1
Invalid data length
Bit 2
Not used
Bit 3
Parity error
Bit 4
Overrun error
Bit 5
Framing error
Bit 6
Time-out
Not used
Programming 93
Contents
1: ON 0: OFF
1: ON 0: OFF
1: ON 0: OFF
1: ON 0: OFF
1: ON 0: OFF
1: ON 0: OFF
1: ON 0: OFF
1: Operating
1: Zero speed
1: Matched
1: Matched
1: Output frequency ≤ L4-01
1: Output frequency ≥ L4-01
1: Startup completed
1: Detected
1: Drive output baseblock
1: Not communication 0: Communication
1: Not communication 0: Communication
1: Detected
1: Lost
1: Retrying

Advertisement

Table of Contents
loading