NetNumen™ U31 R06 Hardware Installation Guide
l
Cut off any surplus parts of cables instead of coiling them.
l
If two O-type terminals are installed, the terminals should be cross-connected (see A
of
Figure
(see B of
O-type terminals must not be overlaid (see C of
cannot be placed on the smaller one (see D of
Figure 6-4 Installation Modes of O-Type Terminals
l
The horizontal distance between power cables (or grounding cables) and other cables
should be greater than 300 mm, see
SJ-20141121113158-006|2014-12-20 (R1.0)
6-4), or one O-type terminal is bent at an angle of 45 degrees or 90 degrees
Figure
6-4).
Figure
6-4). The larger O-type terminal
Figure
Figure
6-5.
6-4
ZTE Proprietary and Confidential
6-4).