Omron I537-E2-01 User Manual page 241

Table of Contents

Advertisement

200 V and 400 V Class Inverters of 22 kW or More
A cooling fan is attached to the top panel inside the Inverter.
The cooling fan can be replaced without removing the Inverter from the installation panel.
Removing the Cooling Fan
1. Remove the terminal cover, Inverter cover, Digital Operator and front cover from the front of the Inverter.
2. Remove the controller bracket to which the cards are mounted. Remove all cables connected to the con-
troller.
3. Remove the cooling fan power cable connectors (CN26 and CN27) from the gate driver positioned at the
back of the controller.
4. Remove the fan cover screws and pull out the fan cover from the Inverter.
5. Remove the cooling fan from the fan cover.
Mounting the Cooling Fan
After attaching a new cooling fan, reverse the above procedure to attach all of the components.
When attaching the cooling fan to the mounting bracket, be sure that the air flow faces the top of the Inverter.
Controller bracket
Controller
Fig 8.2 Cooling Fan Replacement (Inverters of 22 kW or More)
Air flow direction
Fan cover
Connector
Gate driver
Maintenance and Inspection
5
8-

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents