Basic Settings
Switch to the quick programming mode (the QUICK indicator on the Digital Operation should be lit) and then
set the following parameters.
Refer to Chapter 3 Digital Operator and Modes for Digital Operator operating procedures and to Chapter 5
Parameters and Chapter 6 Parameter Settings by Function for details on the parameters.
Parame-
Class
ter Num-
l
l
O
l
l
O
d1-01 to
O
d1-04 and
l
-6
4
Table 4.1 Parameters that must be set
Name
ber
Set the frequency reference input
method.
0: Digital Operator
Reference selec-
b1-01
1: Control circuit terminal (analog
tion
2: RS-422A/485 communications
3: Option Card
Set the run command input method.
0: Digital Operator
Operation
1: Control circuit terminal (sequence
b1-02
method selection
2: RS-422A/485 communications
3: Option Card
Select stopping method when stop com-
mand is sent.
Stopping method
0: Deceleration to stop
b1-03
selection
1: Coast to stop
2: DC braking stop
3: Coast to stop with timer
Set the acceleration time in seconds for
Acceleration time
C1-01
the output frequency to climb from 0% to
1
100%.
Set the deceleration time in seconds for
Deceleration time
C1-02
the output frequency to fall from 100% to
1
0%.
The carrier frequency is set low if the
Carrier fre-
C6-02
motor cable is 50 m or longer or to
quency selection
reduce radio noise or leakage current.
Frequency refer-
ences 1 to 4 and
Set the required speed references for
jog frequency ref-
multi-step speed operation or jogging.
d1-17
erence
Input voltage set-
Set the Inverter's nominal input voltage
E1-01
ting
in volts.
Description
input)
input)
O
Class l : Must be set.
: Set as required.
Setting
Factory
Page
Range
Setting
5-8
6-4
0 to 3
1
6-46
6-54
5-8
6-8
0 to 3
1
6-46
6-54
5-8
0 to 3
0
6-10
5-13
0.0 to 6000.0
10.0 s
6-17
5-13
0.0 to 6000.0
10.0 s
6-17
0 to D, F
F
5-15
d1-01 to
d1-04:
5-16
0 to 120.00 Hz
0.00 Hz
6-6
d1-17:
6.00 Hz
200 V
155 to 255 V
(200 V
(200 V class)
class)
5-18
310 to 510 V
400 V
6-74
(400 V class)
(400 V
class)