AC Reactor
An AC Reactor is used to control harmonics generated by the Inverter or when the power supply capacity is
greatly larger than the Inverter's capacity. It is also used to increase the power factor. Select the AC Reactor
from the following table according to the motor capacity.
Models and Application
The standard models of AC Reactors are listed in the following table.
Inverter
Voltage
Class
200-V Class
400-V Class
-20
9
Max. Appli-
cable Motor
Model No.
Capacity
(kW)
0.4
3G3IV-PUZBAB2.5A4.2MH
0.75
3G3IV-PUZBAB5A2.1MH
1.5
3G3IV-PUZBAB10A1.1MH
2.2
3G3IV-PUZBAB15A0.71MH
3.7
3G3IV-PUZBAB20A0.53MH
5.5
3G3IV-PUZBAB30A0.35MH
7.5
3G3IV-PUZBAB40A0.265MH
11
3G3IV-PUZBAB60A0.18MH
15
3G3IV-PUZBAB80A0.13MH
18.5
3G3IV-PUZBAB90A0.12MH
22
3G3IV-PUZBAB120A0.09MH
30
3G3IV-PUZBAB160A0.07MH
37
3G3IV-PUZBAB200A0.05MH
45
3G3IV-PUZBAB240A0.044MH
55
3G3IV-PUZBAB280A0.038MH
0.4
3G3IV-PUZBAB1.3A18.0MH
0.75
3G3IV-PUZBAB2.5A8.4MH
1.5
3G3IV-PUZBAB5A4.2MH
2.2
3G3IV-PUZBAB7.5A3.6MH
3.7
3G3IV-PUZBAB10A2.2MH
5.5
3G3IV-PUZBAB15A1.42MH
7.5
3G3IV-PUZBAB20A1.06MH
11
3G3IV-PUZBAB30A0.7MH
15
3G3IV-PUZBAB40A0.53MH
18.5
3G3IV-PUZBAB50A0.42MH
22
3G3IV-PUZBAB60A0.36MH
30
3G3IV-PUZBAB80A0.26MH
37
3G3IV-PUZBAB90A0.24MH
45
3G3IV-PUZBAB120A0.18MH
55
3G3IV-PUZBAB150A0.15MH
AC Reactor
Current
Inductance
(A)
(mH)
2.5
4.2
5
2.1
10
1.1
15
0.71
20
0.53
30
0.35
40
0.265
60
0.18
80
0.13
90
0.12
120
0.09
160
0.07
200
0.05
240
0.044
280
0.038
1.3
18.0
2.5
8.4
5
4.2
7.5
3.6
10
2.2
15
1.42
20
1.06
30
0.7
40
0.53
50
0.42
60
0.36
80
0.26
90
0.24
120
0.18
150
0.15
Loss
(W)
15
15
25
30
35
45
50
65
75
90
90
100
110
125
130
15
15
25
35
43
50
50
65
90
90
90
95
110
130
150

Advertisement