DIP Switch S1 and Shunt Connector CN15
The DIP switch S1 and shunt connector CN 15 of the optional terminal board (3G3PV-PETC618120) are
described in this section.
* Note: Refer to Table 2.10 for S1 functions.
**Note: CN15 is not available at the standard terminal board.
An optional terminal board with CN15 Shunt Connector is available.
The standard setting is voltage output.
The functions of DIP switch S1 are shown in the following table.
Name
Function
RS-485 and RS-422 terminating resis-
S1-1
tance
S1-2
Input method for analog input A2
Sinking/Sourcing Mode
The input terminal logic can be switched between sinking mode (0-V common) and sourcing mode (+24V
common) by using the terminals SN, SC and SP. An external power supply is also supported, providing more
freedom in signal input methods.
S1
Terminating resistance*
OFF
ON
Analog input A2 switch
V
I
: Factory settings
Analog output switch**
CN15
Voltage output
Current output
S1
CN15
Fig 2.18 DIP Switch S1 and Shunt Connector CN15
Table 2.10 DIP Switch S1
OFF: No terminating resistance
ON: Terminating resistance of 110 Ω
OFF: 0 to 10 V (internal resistance: 20 kΩ)
ON: 4 to 20 mA (internal resistance: 250 Ω)
Wiring Control Circuit Terminals
Setting
25