Data Tables
The data tables are shown below. The types of data are as follows: Reference data, monitor data and broadcast
data.
Reference Data
The reference data table is shown below. You can both read and write reference data.
Register No.
0000H
0001H
0002H
0003H to 0005H Not used
0006H
0007H
0008H
0009H
000AH to 000EH Not used
-58
6
Reserved
Frequency reference
Bit 0
Run/stop command
Bit 1
Forward/reverse operation
Bit 2
External error
Bit 3
Error reset
Bit 4
ComNet
Bit 5
ComCtrl
Bit 6
Multi-function input command 3
Bit 7
Multi-function input command 4
Bit 8
Multi-function input command 5
Bit 9
Multi-function input command 6
Bit A
Multi-function input command 7
Bits B to F
Not used
Frequency reference (Set units using parameter o1-03)
Not used
Analog output 1 setting (0 V/0 to 11 V/726) → 10V = 660
Analog output 2 setting (0 V/0 to 11 V/726) → 10V = 660
Multi-function contact output setting
Bit 0
Contact output 1 (Terminal M1-M2)
Bit 1
Contact output 2 (Terminal M3-M4)
Bit 2
Not used
Bits 3 to 5
Not used
Bit 6
Set error contact (terminal MA-MC) output using bit 7. 1: ON 0: OFF
Bit 7
Error contact (terminal MA-MC)
Bits 8 to F
Not used
Contents
1: Run 0: Stop
1: Reverse 0: Forward
1: Error (EFO)
1: Reset command
1: ON 0: OFF
1: ON 0: OFF
1: ON 0: OFF