Omron I537-E2-01 User Manual page 211

Table of Contents

Advertisement

When E1-03 is set to F (User-defined V/f pattern), you can set parameters E1-04 to E1-10. If E1-03 is set to
anything other than F, you can only refer to parameters E1-04 to E1-10. If the V/f characteristics are linear, set
E1-07 and E1-09 to the same value. In this case, E1-08 will be ignored.
INFO
Output voltage (V)
Setting Precautions
When the setting is to user-defined V/f pattern, beware of the following points.
When changing control method, parameters E1-07 to E1-10 will change to the factory settings for that con-
trol method.
Be sure to set the four frequencies as follows:
E1-04 (FMAX) ≥ E1-06 (FA) > E1-07 (FB) ≥ E1-09 (FMIN)
Fig 6.46 User-Set V/f Pattern
Individual Functions
Frequency (Hz)
79
6-

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents