Loopback Test
The loopback test returns command messages directly as response messages without changing the contents to
check the communications between the master and slave. You can set user-defined test code and data values.
The following table shows a message example when performing a loopback test with the slave 1 Inverter.
Command Message
Slave address
01H
Function code
08H
Higher
00H
Test Code
Lower
00H
Higher
A5H
Data
Lower
37H
Higher
DAH
CRC-16
Lower
8DH
Writing to Multiple Storage Registers
Write the specified data to the registers from the specified addresses. The written data must be consecutive,
starting from the specified address in the command message: Higher 8 bits, then lower 8 bits, in storage regis-
ter address order.
The following table shows an example of a message when forward operation has been set at a frequency refer-
ence of 60.0 Hz in the slave 1 Inverter by the PLC.
Command Message
Slave Address
01H
Function Code
10H
Higher
00H
Start
Address
Lower
01H
Higher
00H
Quantity
Lower
02H
No. of data
04H
Higher
00H
Lead data
Lower
01H
Higher
02H
Next data
Lower
58H
Higher
63H
CRC-16
Lower
39H
Set the number of data specified using command messages as quantity of specified messages x 2. Handle
response messages in the same way.
IMPORTANT
Response Message
(During Normal Operation)
Slave address
01H
Function code
08H
Higher
00H
Test Code
Lower
00H
Higher
A5H
Data
Lower
37H
Higher
DAH
CRC-16
Lower
8DH
Response Message
(During Normal Operation)
Slave Address
01H
Function Code
10H
Higher
00H
Start
Address
Lower
01H
Higher
00H
Quantity
Lower
02H
Higher
10H
CRC-16
Lower
08H
* No. of data = 2 x (quantity)
Individual Functions
Response Message
(During Error)
Slave address
01H
Function code
89H
Error Code
01H
Higher
86H
CRC-16
Lower
50H
Response Message
(During Error)
Slave Address
01H
Function Code
90H
Error code
02H
Higher
CDH
CRC-16
Lower
C1H
57