Omron I537-E2-01 User Manual page 195

Table of Contents

Advertisement

Error Codes
The following table shows RS-422A/485 communications error codes.
Error Code
Function code error
01H
A function code other than 03H, 08H or 10H has been set by the PLC.
Invalid register number error
02H
• The register address you are attempting to access is not recorded anywhere.
• With broadcast sending, a start address other than 0000H, 0001H or 0002H has been set.
Invalid quantity error
03H
• The number of data packets being read or written is outside the range 1 to 16.
• In write mode, the number of data packets in the message is not No. of packets x 2.
Data setting error
• A simple upper limit or lower limit error has occurred in the control data or when writing parame-
21H
ters.
• When writing parameters, the parameter setting is invalid.
Write mode error
• Attempting to write parameters to the inverter during operation.
• Attempting to write via ENTER commands during operation.
22H
• Attempting to write parameters other than A1-00 to A1-05, E1-03 or 02-04 when warning alarm
CPF03 (defective EEPROM) has occurred.
• Attempting to write read-only data.
Writing during main circuit undervoltage (UV) error
23H
• Writing parameters to the inverter during UV (main circuit undervoltage) alarm.
• Writing via ENTER commands during UV (main circuit undervoltage) alarm.
Writing error during parameters processing
24H
Attempting to write parameters while processing parameters in the Inverter.
Slave Not Responding
In the following cases, the slave will ignore the write function.
When a communications error (overrun, framing, parity or CRC-16) is detected in the command message.
When the slave address in the command message and the slave address in the Inverter do not agree.
When the data that configures the message and the data time length exceeds 24 bits.
When the command message data length is invalid.
Application Precautions
If the slave address specified in the command message is 0, all slaves execute the write function, but do not
return response messages to the master.
INFO