Stopping Methods
Selecting the Stopping Method when a Stop Command is Input
There are four methods of stopping the Inverter when a stop command is input:
•
Deceleration to stop
•
Coast to stop
DC braking stop
•
Coast to stop with timer
•
Set parameter b1-03 to select the Inverter stopping method.
Related Parameters
Param-
eter-
number
Stopping method selec-
b1-03
Zero speed level (DC
injection braking start-
b2-01
DC injection braking cur-
b2-02
DC injection braking
b2-04
-10
6
Name
LCD Display
Select stopping method when stop com-
tion
mand is sent.
0: Deceleration to stop
1: Coast to stop
2: DC braking stop (Stops faster than coast
Stopping Method
to stop, without regenerative operation.)
3: Coast to stop with timer (Run commands
are ignored during deceleration time.)
Set the frequency to start the DC injection
braking in units of Hz when deceleration to
ing frequency)
stop is selected.
DC injection braking starts from E1-09
DCInj Start Freq
when b2-01 < E1-09.
Set the DC injection braking current as a
rent
percentage, taking the Inverter rated current
DCInj Current
as 100%.
Set the DC injection braking time at stop.
time at stop
Use when stopping if rotations continue due
to momentum.
Set to 0.00 to disable DC injection braking
DCInj Time @Stop
time at stop.
Setting
Description
Range
0 to 3
0.0 to
10.0
0 to
100
0.00
to
10.00
Change
Factory
during
Access
Setting
Opera-
Level
tion
0
No
Q
0.5 Hz
No
A
50%
No
A
0.50 s
No
A