Param-
eter
Number
E2-01
H4-02
H4-05
L1-01
L3-04
* 1. The factory setting depends on the Inverter capacity.
* 2. These are values for a 200 V class Inverter. Values for a 400 V class Inverter are double.
* 3. After autotuning, E1-13 will contain the same value as E1-05.
* 4. The factory setting depends on the Inverter capacity. (The value for a 200 V Class Inverter for 0.4 kW is given.)
* 5. The setting range is from 10% to 200% of the Inverter rated output current. (The value for a 200 V Class Inverter for 0.4 kW is given.)
-6
5
Name
Description
LCD Display
Set the motor rated current in Amps.
Motor rated
current
This set value becomes the base value
for motor protection, torque limit and
torque control. It is an input data for
Motor Rated
FLA
autotuning.
Gain (termi-
Set the voltage level gain for multi-
nal FM)
function analog output 1.
Set the number of multiples of 10 V to
be output as the 100% output for the
monitor items. Voltage output from
Terminal FM
Gain
the terminals, however, have a 10 V
max. meter calibration function.
Gain (termi-
nal AM)
Set the voltage level gain for multi-
function analog output 2.
Terminal AM
Gain
Set to enable or disable the motor
overload protection function using the
electronic thermal relay.
0: Disabled
1: General-purpose motor protection
Motor protec-
In some applications when the Inver-
tion selection
ter power supply is turned off, the
thermal value is reset, so even if this
parameter is set to 1, protection may
not be effective.
When several motors are connected to
one Inverter, set to 0 and ensure that
each motor is equipped with a protec-
MOL Fault
tion device.
Select
Stall preven-
0: Disabled (Deceleration as set. If
tion selection
deceleration time is too short, a
during decel-
eration
main circuit overvoltage may
result.)
1: Enabled (Deceleration is stopped
when the main circuit voltage
exceeds the overvoltage level.
Deceleration restarts when voltage
is returned.)
2: Intelligent deceleration mode
StallP Decel
(Deceleration rate is automatically
Sel
adjusted so that in Inverter can
decelerate in the shortest possible
time. Set deceleration time is disre-
garded.)
When a braking option (Braking
Resistor, Braking Resistor Unit, Brak-
ing Unit) is used, always set to 0 to 2.
Change
Setting
Factory
during
Access
Range
Setting
Opera-
Level
tion
0.32 to
1.90 A
No
Q
6.40
*4
*5
0.0 to
100%
Yes
Q
1000.0
0.0 to
50%
Yes
Q
1000.0
0 or 1
1
No
Q
0 to 2
1
No
Q
RS-422A/
485 Reg-
ister
30EH
41EH
421H
480H
492H