9 DEDICATED INSTRUCTIONS

9.4 INPUT Instruction

Set
Internal device
data
(System, user)
Bit
Word
(S)
(D1)
(D2)
[Instruction
code]
INPUT
Set data
Set data
(D1)
(D2)
Control data
Device
(S) + 0
Receive channel
(S) + 1
Reception result
(S) + 2
Receive data count
Allowable number of
(S) + 3
receive data
9 - 8
This instruction receives data in any message format specified by the user using the
non procedure protocol.
MELSECNET/H,
MELSECNET/10
File register
Direct J \
Bit
[Executing
condition]
Command
Start I/O signal of the module
Un
(00 to FE: Top two-digit when I/O signals are expressed in 3-digit.)
(S)
Head number of the devices in which control data is stored.
Head number of the devices in which receive data is stored.
Bit device number to be turned on at completion of execution.
The file register per local device and program cannot be used as the set data.
Item
• Set receive channel
1: Channel 1 (CH1 side)
2: Channel 2 (CH2 side)
• Reception result by an INPUT instruction are
stored.
0:
Other than 0: Error code
• Receive data count is stored.
• Set the allowable number of words for received
data that can be stored in (D1).
POINT
(1) The command of G.INPUT cannot be converted into pulse.
(2) G.INPUT should be executed while the read request of the input/output signal
is turned on.
Applicable device
Special module
U \G
Word
Un
G.INPUT
Description
Set data
Normal
1
2
MELSEC-Q
Index register Zn
Constant Others
(S)
(D1)
(D2)
Set by
User
User,
system
System
System
Setting range
1, 2
0 or more
1 or more
Data type
BIN16 bit
Device name
Bit
3
Set by
User
System
System
User
9 - 8