8 UTILITY PACKAGE (GX Configurator-SC)
8 - 12
POINT
(1) Saving the intelligent function module parameter files
Since files cannot be saved using the GX Developer project save operation,
save the files on the module selection screen for parameter setting described
above.
(2) Reading from and writing to PLC operations for the intelligent function module
parameters using GX Developer
(a) After the intelligent function module parameters are saved in a file, they
can be read from and written into the PLC.
(b) Set the target PLC using the GX Developer [Online]
Only use the control PLC for the Q series C24 to write the intelligent
function module parameters for a multiple CPU system to the PLC.
(c) Use the GX Developer for PLC reading or PLC writing the intelligent
function module parameters at the remote I/O station.
GX Configurator-SC can not be used.
(3) Checking for the required utility
The head I/O is displayed in the Intelligent function module utility setting
screen, but a " " may be displayed for the model name.
This means that either the required utility is not installed or that the utility
cannot be started from the GX Developer.
Check for the required utility in [Tools] - [Intelligent function utility] - [Utility
list...] in GX Developer, and set it.
MELSEC-Q
[Transfer setup].
8 - 12