en | Off-board outputs
11

Off-board outputs

The control panel supports off-board outputs using the B308 Octo-output Module.
11.1

B308 Octo-output Module

The B308 is an eight output expansion device that connects to control panels through the
SDI2 bus. This module is supervised for the connection to the SDI2 bus. It provides eight
independently controlled outputs. Each output can operate as either normally open or
normally closed. You can configure the function for each output on the module individually.
Refer to Output Parameters in RPS Help or the control panel Program Entry Guide.
B5512 control panels support up to 5 modules to provide 40 outputs. B4512 control panels
support up to 3 modules to provide 24 outputs.
The B3512 does not support the B308 module.
B308 Octo-output Modules connect to the SDI2 bus on the control panel using terminals PWR,
A, B, and COM, or using the SDI2 interconnect wiring connector. You can connect more than
one module to the control panel by wiring them in parallel. This section includes basic
installation instructions. For detailed installation instructions, refer to the Octo-output Module
(B308) Installation and Operation Guide.
Notice!
Do not connect fire and non-fire devices to the same B308 Octo-output Module.
Outputs overview
Each module output provides a Form C dry contact rated for .001 to 1.0 A at 5 to 24 VDC
(resistive load). Normally-open, common, and normally-closed terminals are available for each
relay output. When an individual output is activated, continuity exists between the normally
open and common terminals. When the output is not activated, continuity exists between the
normally closed and common terminals.
11.1.1

SDI2 address settings

Notice!
The module reads the address switch setting only during module power up. If you change the
setting after you apply power to the module, you must cycle the power to the module in order
for the new setting to take effect.
If multiple B308 modules reside on the same system, each B308 module must have a unique
address.
The number of outputs allowed by the control panel determines the valid addresses.
Octo-output module number
01
02
03
04*
2015.07 | 12 | F.01U.287.180
Installation and System Reference Guide
Supported outputs
11 – 18
21 – 28
31 – 38
41 – 48*
Control Panel
Bosch Security Systems, Inc.