158
en | Reporting and device number information
User ID type
Keypad display
Service User
0
Standard Users
1...50
Time Sync
5001
RPS User
5002
Automation User
5003
Keyswitch
5004
No User Specified
User not displayed
21.6

Keypad alarm virtual point numbers (ppp, pppp)

Special point numbers identify the originator of manually created keypad alarm events. All
special point numbers are defined in the table below.
Notice!
The point numbers for manually created keypad alarm events are changed in control panel
firmware version 3.01.
Originating keypad
Keypad 1
Keypad 2
Keypad 3
Keypad 4
Keypad 5
Keypad 6
Keypad 7
Keypad 8
2015.07 | 12 | F.01U.287.180
Contact ID
Modem format
reporting
F00
0
001...50
1...50
F01
5001
F02
5002/none
F03
5003/none
F04
5004
000
0xFFFF (displays blank)
Control panel firmware
version 2.04 and lower,
reported point number
330
340
350
360
370
380
390
400
Installation and System Reference Guide
User text
"SERVICE USER"
{configured text}
"AUTO TIME SYNC"
"BY RPS"
"BY AUTOMATION"
"BY KEYSWITCH"
{no text}
Control panel firmware
version 3.01 and higher,
reported point number
901
902
903
904
905
906
907
908

Bosch Security Systems, Inc.