Fire Applications - Bosch B5512 Reference Manual

Hide thumbs Also See for B5512:
Table of Contents

Advertisement

Control Panel
Safe and Vault protective circuits
To test the devices that protect the safe(s) or vault(s) without sounding the bell, specify the
devices' points as controlled zones and supervised for trouble conditions. Refer to Point Index
in RPS Help or the control panel's Program Entry Guide more information.
Bell configuration
Bell test
Exit delay
Do not program the control panel's maximum exit delay longer than 30 seconds.
18.1.3

Fire applications

You can use UL Listed fire initiating devices not requiring electrical compatibility evaluation in
any application. For example, the four-wire smoke detectors, heat detectors, waterflow
switches, and manual pull stations are suitable fire initiating devices. Consult the individual
component specification and installation documents to determine suitability.
Notice!
UL requires that the control panel supervises any device powered from a power output.
Notice!
The control panel does not support multiple detectors in alarm. The control panel is
compatible with detectors with optional features. Do not mix detectors from different
manufacturers on the same circuit.
Four-wire smoke detectors
When using four-wire smoke detectors, install a power supervision device according to the
manufacturer's instructions. You can connect any number of four-wire smoke detectors to the
control panel (subject to available auxiliary power).
The Reset Sensor command is available from the keypads when the Reset Sensor is enabled.
Connect the smoke detectors to a suitable interface such as the B208 Octo-input Module or
on-board point to meet UL and NFPA requirements.
Notification Appliance Circuit (NAC)
Refer to Notification appliance circuit wiring, page 83.
Bosch Security Systems, Inc.
UL 365 requires a bell time of 15 to 30 min. The Rothenbuhler 5110 Bell provides
selectable bell time through manipulation of its jumpers. Refer to the manufacturer's
installation instructions for more information.
In addition to the jumper settings inside the bell, you can activate the control panel for a
bell time of 15 min.
UL 365 requires a Bell Test at arming and you must enable it in control panel
programming.
Refer to the various bell parameters in RPS Help or the control panel's Program Entry
Guide for more bell time and test programming information.
To enable the bell test feature, you enable an unused area of the control panel. Enable
the bell test feature for the unused area only. Program OUTPUT B as the area bell output
for the unused area.
Make all passcodes with authority to arm the safe or vault and also send a Closing Report
valid in this area. Program the area for a five-second exit delay.
To complete the installation for this feature, connect the output to a D134 Dual Relay
Module.
Installation and System Reference Guide
Approved applications | en
2015.07 | 12 | F.01U.287.180
93

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

B3512B5512eB4512eB3512eB4512

Table of Contents