Table 29 Non-operating environmental specifications (Continued)
Specification
Humidity
Shock
Vibration

Electrical requirements

Site wiring and power requirements
Each enclosure requires two power supply modules for redundancy. If full redundancy is required, use a
separate power source for each module. The AC power supply unit in each power supply module is
auto-ranging and is automatically configured to an input voltage range from 100-240 VAC with an input
frequency of 50/60 Hz. The power supply modules meet standard voltage requirements for both U.S. and
international operation. The power supply modules use standard industrial wiring with line-to-neutral or
line-to-line power connections.
Power cable requirements
Each enclosure requires two power cables designed for use with the enclosure power supply module. Each
power cable connects one of the power supply modules to an independent, external power source. To
ensure power redundancy, connect the two power cables to two separate circuits; for example, to one
commercial circuit and one uninterruptible power source (UPS).
Range
Up to 93% RH @ 104ºF (40ºC) non-condensing
15.0 g, 1 1 ms, ½ sine pulses, X, Y, Z
(Shaped-spectrum)
2.8 Hz to 365.4 Hz, 0.852 G rms total (horizontal)
2.8 Hz to 365.4 Hz, 1.222 G rms total (vertical)