SiUS181305E
4.2
Freeze-up Protection Control or Heating Peak-cut Control
A5
Error Code
Freeze-up protection control
Method of Error
Detection
Heating peak-cut control
Freeze-up protection control
Error Decision
Conditions
Heating peak-cut control
Short-circuited air
Supposed
Clogged air filter of the indoor unit
Causes
Dust accumulation on the indoor heat exchanger
Defective indoor heat exchanger thermistor
Defective indoor unit PCB
Troubleshooting
During cooling operation, the freeze-up protection control (operation halt) is activated according
to the temperature detected by the indoor heat exchanger thermistor.
During heating operation, the temperature detected by the indoor heat exchanger thermistor is
used for the heating peak-cut control (operation halt, outdoor fan stop, etc.)
During cooling operation, the indoor heat exchanger temperature is below 0°C (32°F).
During heating operation, the indoor heat exchanger temperature is above 65°C (149°F).
Troubleshooting for CTXS, FTXS, CDXS, FDXS Series
158